The drop-out fuse is a crucial short-circuit protection device widely used in 10kV distribution line branches and transformers. Manufactured in China, our drop-out fuses are designed to minimize power outage scope when installed on branches, with a unique breaking point serving as an isolating switch for safe maintenance. When mounted on transformers, they provide essential primary protection. As a leading supplier in the industry, our factory offers cost-effective solutions that ensure easy operation and robust outdoor adaptability. These features have made our drop-out fuses a popular choice for protecting and switching operations on the primary side of 10kV distribution lines and transformers. Choose our reliable products for superior performance and safety

    Working Principle

    The moving contacts at both ends of the fuse tube are fastened by the fuse (melting element). After pushing the upper moving contact into the protruding part of the "duckbill", the upper static contact made of phosphor copper sheet etc. presses against the upper moving contact, so that the fuse tube is firmly clamped in the "duckbill". When the short-circuit current passes through and fuses the fuse, an electric arc is generated. The steel paper tube lined inside the fuse tube produces a large amount of gas under the action of the electric arc. Since the upper end of the fuse tube is sealed, the gas is sprayed downward to extinguish the electric arc. Due to the fuse melting, the upper and lower moving contacts of the fuse tube lose the tension of the fuse. Under the action of the fuse tube's own gravity and the spring sheets of the upper and lower static contacts, the fuse tube falls rapidly, disconnecting the circuit and cutting off the faulty line section or faulty equipment.

    Applicable Environment

    The 10kV drop-out fuse is suitable for outdoor places where the ambient air is free of conductive dust, corrosive gases, flammable, explosive and other hazardous environments, and the annual temperature difference ratio is within ±40℃. Its selection is based on two parameters: rated voltage and rated current, that is, the rated voltage of the fuse must match the rated voltage of the protected equipment (line).

    Installation Tips
    • 1 During installation, the melting element should be tightened (so that the melting element is subjected to a tension of about 24.5N), otherwise it is easy to cause contact heating.
    • 2 The fuse should be firmly installed on the crossarm (frame) without any shaking or wobbling.
    • 3 The fuse tube should have a downward inclination angle of 25°±2° to facilitate the rapid fall of the fuse tube by its own weight when the melting element fuses.
    • 4 The fuse should be installed on a crossarm (frame) with a vertical distance of not less than 4m from the ground. If installed above the distribution transformer, it should maintain a horizontal distance of more than 0.5m from the outermost contour boundary of the distribution transformer to prevent other accidents caused by the falling of the fuse tube.
    • 5 The length of the fuse tube should be adjusted appropriately. It is required that after closing, the duckbill tongue can hold more than two-thirds of the contact length to avoid accidental self-falling during operation. The fuse tube should not push the duckbill to death to prevent the fuse tube from failing to fall in time after the melting element fuses.
    • 6 The melting element used must be a standard product from regular manufacturers and have a certain mechanical strength. Generally, the melting element is required to withstand a tension of at least 147N.
    • 7 The 10kV drop-out fuse is installed outdoors, requiring a phase-to-phase distance greater than 70cm.
    Applicable Environment

    div容器

    Frequently Asked Questions
    QWhat is the working principle of a 10kV drop-out fuse?
    AWhen a short-circuit current fuses the melting element, an electric arc is generated inside the fuse tube. The steel paper lining produces gas that extinguishes the arc. The fuse tube then loses tension and falls under gravity, disconnecting the circuit and isolating the faulty section or equipment.
    QWhat environments are 10kV drop-out fuses suitable for?
    AThey are designed for outdoor use in environments free of conductive dust, corrosive gases, and flammable or explosive hazards. The annual temperature difference must remain within ±40℃ for safe and reliable operation.
    QWhat inclination angle should the fuse tube be installed at?
    AThe fuse tube must be installed at a downward inclination angle of 25°±2°. This ensures the tube falls quickly under its own weight when the melting element fuses, reliably disconnecting the circuit.
    QWhat is the minimum installation height for a 10kV drop-out fuse?
    AThe fuse must be installed at a vertical distance of not less than 4m from the ground. When mounted above a distribution transformer, a horizontal clearance of more than 0.5m from the transformer's outermost boundary is required to prevent secondary accidents from a falling fuse tube.
    QHow should the melting element be tensioned during installation?
    AThe melting element should be tightened to approximately 24.5N of tension during installation. Insufficient tension can lead to contact heating. The element must also be a standard product capable of withstanding at least 147N of mechanical tension.
    QWhat is the required phase-to-phase distance for outdoor installation of a 10kV drop-out fuse?
    AFor outdoor installations, the phase-to-phase distance must be greater than 70cm. Additionally, after closing, the duckbill tongue should hold more than two-thirds of the contact length to prevent accidental self-falling during normal operation.