China 15kV Drop-Out Fuse Cutout - Reliable Suppliers & Factory for 10kV Distribution Line Protection
When the short-circuit current passes through and fuses the fuse, an electric arc is generated. The steel paper tube lined inside the fuse tube produces a large amount of gas under the action of the electric arc. Since the upper end of the fuse tube is sealed, the gas is sprayed downward to extinguish the electric arc.
Due to the fuse melting, the upper and lower moving contacts of the fuse tube lose the tension of the fuse. Under the action of the fuse tube's own gravity and the spring sheets of the upper and lower static contacts, the fuse tube falls rapidly, disconnecting the circuit and cutting off the faulty line section or faulty equipment.
Its selection is based on two key parameters:
- 1 Rated Voltage — The rated voltage of the fuse must match the rated voltage of the protected equipment (line).
- 2 Rated Current — Must be correctly selected based on the load requirements of the protected circuit.
- 1 During installation, the melting element should be tightened so that it is subjected to a tension of about ~24.5N, otherwise it is easy to cause contact heating.
- 2 The fuse should be firmly installed on the crossarm (frame) without any shaking or wobbling.
- 3 The fuse tube should have a downward inclination angle of 25° ± 2° to facilitate the rapid fall of the fuse tube by its own weight when the melting element fuses.
- 4 The fuse should be installed on a crossarm (frame) with a vertical distance of ≥ 4m from the ground. If installed above the distribution transformer, maintain a horizontal distance of > 0.5m from the outermost contour boundary of the transformer to prevent accidents caused by the falling of the fuse tube.
- 5 After closing, the duckbill tongue must hold more than 2/3 of the contact length to avoid accidental self-falling during operation. The fuse tube should not push the duckbill to dead-stop to prevent the fuse tube from failing to fall in time after the melting element fuses.
- 6 The melting element used must be a standard product from regular manufacturers with sufficient mechanical strength. Generally, the melting element is required to withstand a tension of at least 147N.
- 7 The 10kV drop-out fuse is installed outdoors, requiring a phase-to-phase distance of > 70cm.