+86 15657752999
GW13-15 Isolating Switch
Product Overview
Product Overview
The GW13-15 Isolating Switch is a manually operated disconnect switch engineered for outdoor overhead distribution systems. Designed for circuit sectionalizing and isolation at voltages up to 38kV, it delivers dependable performance with rated currents of 400A or 630A. Available in both 12kV and 36kV versions, the switch features a self-locking mechanism and a 90-degree blade opening for clear visual isolation. Constructed with silver-plated copper components and your choice of porcelain or polymer insulators, it meets IEC 62271-102 standards and operates reliably in heavy pollution environments at altitudes up to 1000 meters and ambient temperatures up to 40°C.
Product Features
Product Features
◆ Wide voltage range with 12kV and 36kV rated options
◆ High mechanical durability with self-locking mechanism
◆ Clear visual break with 90-degree blade opening position
◆ Excellent insulation performance with lightning impulse withstand up to 170kV
◆ Available with porcelain or polymer insulators to suit different environments
◆ Corrosion-resistant construction with silver-plated copper current-carrying parts
◆ Robust hot-dip galvanized steel channel base for long-term outdoor use
◆ Flexible configuration with optional mounting brackets, terminal clamps, and loadbuster hooks
◆ Compliant with international standard IEC 62271-102:2001
Product Advantages
Product Advantages
● Enhanced Safety: The 90-degree blade opening and self-locking mechanism provide secure visual isolation, protecting personnel during maintenance.
● Reliable Performance: High short-circuit withstand capability (up to 20kA) and excellent insulation ratings ensure stable operation under fault conditions.
● Weather Resistance: Designed for heavy pollution areas and wet conditions, with verified dry and wet power frequency withstand voltage performance.
● Durable Materials: Silver-plated copper blades and brass/copper terminal pads offer superior conductivity and long-term corrosion resistance.
● Easy Installation: Lightweight design with single carton packaging and optional pre-assembled accessories simplifies on-site setup.
● Versatile Application: Compatible with overhead distribution systems and customizable with loadbuster hooks for load-breaking operations.
Applications
Applications
◆ Outdoor overhead distribution line sectionalizing
◆ Circuit isolation during maintenance and repair work
◆ Substation feeder isolation in medium-voltage networks
◆ Industrial and utility power distribution systems
◆ Rural and urban overhead line applications in heavy pollution environments
Technical parameter
Technical parameter
| Electrical characteristics | Specification | Unit | |
| Rated voltage of Disconnector | 12 | 36 | kV |
| Rated current | 400 / 630 | A | |
| Rated frequency | 50 | Hz | |
| Lighting Impulse withstand voltage | 95 | 170 | kV |
| Power frequency withstand voltage in 1 min (Dry) | 42 | 70 | kV |
| Power frequency withstand voltage in 10 s (Wet) | 36 | 60 | kV |
| Rated short circuit withstand current | 16(for 400A)/ 20(for 630A) | kA | |
| Rated short circuit withstand time | 3 | s | |
| Rated peak withstand current | 40(for 400A)/ 50(for 630A) | kA | |
| Creepage | 25 | 20 | mm/kV |
| Blade stopped degree in opening position | 90 | DegreeDegree | |
| Spare parts | |
| Operating Mechanism | with |
| Arcing distinguishing chamber | with/without |
| Operating rod length | Customerized |
| Material | |
| Terminal pads | Brass/Copper plated by silver |
| Blade | Copper plated by silver |
| Insulator | Porcelain/Polymer |
| Channel Base | Steel hot galvanized |
| Operating eye | Brass |
| Service conditions | ||
| Environment maximum temperature | 40 | ℃ |
| Pollution level | Heavy | |
| Altitude | ≤1000 | Meter |