+86 15657752999
GW13-36 Isolating Switch
Product Overview
Product Overview
The GW13-36 Isolating Switch is a high-voltage outdoor disconnect switch purpose-built for 36kV overhead distribution networks. Operating as a manually actuated isolating device, it provides visible circuit separation for maintenance safety and network sectionalizing. With a rated current of 630A and peak withstand current of 50kA, the switch is engineered for robust fault-handling capability. Its defining feature is the 160-degree blade opening angle, offering superior visual verification of open-circuit status. Available with either porcelain or polymer insulators and built on a hot-dip galvanized steel base, the GW13-36 is ideal for utilities and industrial operators requiring rugged, standards-compliant isolation equipment for medium-voltage outdoor applications.
Product Features
Product Features
◆ High short-circuit withstand rating of 20kA for 3 seconds
◆ Peak withstand current capability of 50kA
◆ Dual insulator options: porcelain for traditional applications or polymer for lightweight durability
◆ Silver-plated copper blades and terminal pads for optimal conductivity
◆ Self-locking mechanism prevents unintended operation
◆ Hot-dip galvanized steel channel base with excellent outdoor corrosion resistance
◆ Compatible with optional loadbuster hooks for load-breaking capability
Product Advantages
Product Advantages
● Superior Visual Verification: The 160-degree blade opening provides an unmistakable visual break, significantly enhancing operator safety during maintenance procedures.
● Heavy-Duty Fault Handling: With 20kA short-circuit withstand and 50kA peak withstand ratings, the switch remains stable and undamaged under severe fault conditions.
● Proven Insulation Performance: Lightning impulse withstand of 170kV and wet/dry power frequency withstand voltages ensure reliable insulation coordination in exposed outdoor installations.
● Material Excellence: Silver-plated copper current path minimizes contact resistance, reduces hot spots, and extends operational service life.
● Heavy Pollution Readiness: Designed for heavy pollution environments, making it suitable for coastal, industrial, and high-contamination zones.
Applications
Applications
◆ Primary isolation for 36kV outdoor overhead distribution feeders
◆ Visible open-point isolation at utility network sectionalizing points
◆ Industrial plant power supply disconnection for maintenance safety
◆ Rural overhead network isolation points requiring durable, low-maintenance switches
◆ Integration into overhead systems requiring loadbuster-compatible isolation devices
Technical parameter
Technical parameter
| Electrical characteristics | Specification | Unit | |
| Rated voltage of Disconnector | 12 | 36 | kV |
| Rated current | 630 | A | |
| Rated frequency | 50 | Hz | |
| Lighting Impulse withstand voltage | 95 | 170 | kV |
| Power frequency withstand voltage in 1 min (Dry) | 42 | 70 | kV |
| Power frequency withstand voltage in 10 s (Wet) | 36 | 60 | kV |
| Rated short circuit withstand current | 20 | kA | |
| Rated short circuit withstand time | 3 | s | |
| Rated peak withstand current | 50 | kA | |
| Creepage | 25 | 20 | mm/kV |
| Blade stopped degree in opening position | 160 | DegreeDegree | |
| Spare parts | |
| Mounting bracket | with/without |
| Terminal clamp | with/without |
| Loadbuster Hook | with/without |
| Self locking Mechanism | withwith |
| Material | |
| Terminal pads | Brass/Copper plated by silver |
| Blade | Copper plated by silver |
| Insulator | Porcelain/Polymer |
| Channel Base | Steel hot galvanized |
| Service conditions | ||
| Environment maximum temperature | 40 | ℃ |
| Pollution level | Heavy | |
| Altitude | ≤1000 | Meter |
Inquire Now!